    摘要:

    为了解决空气源热泵除霜过程中能量来源不足而导致的各种除霜问题,提出了空气源热泵相变蓄能逆循环除霜方法.对一台额定功率为850 W的家用空气源热泵进行改造,并在人工模拟室内外环境的条件下进行实验.实验结果表明:蓄能除霜可以有效地提高除霜期间压缩机的吸排气压力,缩短除霜时间,减少除霜能耗.相对于常规除霜,在实验条件下,蓄能除霜可以分别提高压缩机吸排气压力0.15和0.25 MPa,缩短除霜时间60%.

    Abstract:

    This study is concerned with a new reverse-cycle hot gas method using phase change thermal energy storage (TES) to eliminate frost in an air-source heat pump (ASHP), which can effectively solve the shortage of defrosting energy. The feasibility of defrosting was investigated through experiments and the modes' performances were compared with a nominal 850 W capacity ASHP system conventional reverse-cycle hot gas defrosting method. The results have indicated that thermal energy storage based reverse-cycle hot gas method can improve the discharge and suction pressure and shorten defrosting time in defrosting. In defrosting operation, the TES defrosting method can improve discharge and suction pressure by 0.25 MPa and 0.15 MPa respectively, and shorten defrosting time by 60% in the tested environment, relative to the conventional reverse-cycle hot gas defrosting method.

    参考文献
    相似文献
    引证文献
文章指标
  • PDF下载次数:
  • HTML阅读次数:
  • 摘要点击次数:
  • 引用次数:
引用本文

董建锴,姜益强, 姚 杨,胡文举.空气源热泵相变蓄能除霜特性实验研究[J].湖南大学学报:自然科学版,2011,38(1):18~22

复制
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期:
  • 出版日期:
作者稿件一经被我刊录用,如无特别声明,即视作同意授予我刊论文整体的全部复制传播的权利,包括但不限于复制权、发行权、信息网络传播权、广播权、表演权、翻译权、汇编权、改编权等著作使用权转让给我刊,我刊有权根据工作需要,允许合作的数据库、新媒体平台及其他数字平台进行数字传播和国际传播等。特此声明。
关闭