防火涂料对高强混凝土高温后氯离子渗透性影响
DOI:
作者:
作者单位:

作者简介:

通讯作者:

基金项目:


Influence of Fire Insulation on the Chloride Ion Permeability of High Strength Concrete after High Temperature
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
    摘要:

    通过5组外包不同厚度防火涂料的C80高强混凝土试块的高温后氯离子渗透试验,研究了氯离子渗透性随涂料厚度的变化情况.试验结果表明:当防火涂料厚度≥30 mm时,高温后氯离子渗透性基本不变;当防火涂料厚度为20~25 mm时,高温后氯离子渗透性低于常温C50混凝土;当防火涂料厚度为15 mm时,高温后氯离子渗透性相对较高.综合考虑后认为,厚度20 mm的防火涂料可同时发挥抑制高强混凝土高温爆裂和降低高温后高强混凝土氯离子渗透性的双重作用.

    Abstract:

    Five groups of high strength concrete (HSC) specimens with a 28-day cubic compressive strength of 82.6 MPa and with fire insulation were tested, and the influence of the thickness of fire insulation on the chloride ion permeability of HSC after high temperature was discussed. Test results have shown that, in the case that the fire insulation thickness is 30 mm, the chloride ion permeability of HSC after high temperature is almost the same as that at room temperature; in the case that the fire insulation thickness is 20~25 mm, the chloride ion permeability of HSC after high temperature is still lower than that of C50 concrete at room temperature; and in the case that the fire insulation thickness is 15 mm, the chloride ion permeability of HSC after high temperature is relatively large. It can be concluded that fire insulation with a thickness of 20 mm is effective both for the inhibition of explosive spalling of HSC at elevated temperature and for the reduction of the chloride ion permeability of HSC after high temperature.

    参考文献
    相似文献
    引证文献
文章指标
  • PDF下载次数:
  • HTML阅读次数:
  • 摘要点击次数:
  • 引用次数:
引用本文

吴波 ,周鹏,吴耀鹏.防火涂料对高强混凝土高温后氯离子渗透性影响[J].湖南大学学报:自然科学版,2013,40(1):9~14

复制
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期:
  • 出版日期:
作者稿件一经被我刊录用,如无特别声明,即视作同意授予我刊论文整体的全部复制传播的权利,包括但不限于复制权、发行权、信息网络传播权、广播权、表演权、翻译权、汇编权、改编权等著作使用权转让给我刊,我刊有权根据工作需要,允许合作的数据库、新媒体平台及其他数字平台进行数字传播和国际传播等。特此声明。
关闭