+高级检索
基于形状因子的辐射地板传热量计算等效热阻模型
DOI:
作者:
作者单位:

作者简介:

通讯作者:

基金项目:


An Equivalent Thermal Resistance Model to Calculate the Heat Transfer of Radiant Floor Heating and Cooling Systems Using Shape Factor
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
    摘要:

    对辐射地板传热过程进行分析,提出了基于形状因子的辐射地板传热量计算等效热阻模型.为了验证简化模型的合理性,采用数值模拟计算结果进行验证,并与标准手册中采用的简化模型计算结果进行对比分析.结果表明,当管间距变化范围为50~250 mm,换热管上端填充层厚度变化范围为25~65 mm及热水平均温度变化范围为25~45 ℃时,ISO标准幂函数计算模型、ASHRAE手册平面肋片模型及地暖设计手册等效热阻模型计算结果与数值模拟计算结果相对误差均较大,最大分别为20.2%,30.4%和22.8%,而本文提出的基于形状因子的等效热阻模型计算结果与数值模拟计算结果相对误差较小,最大不超过3%;当管间距变化范围为50~200 mm,换热管上端填充层厚度变化范围为15~55 mm及冷水平均温度变化范围为10~20 ℃时,ISO标准幂函数计算模型、ASHRAE手册平面肋片模型及地暖设计手册等效热阻模型计算结果与数值模拟计算结果相对误差也均较大,最大分别为80.1%,17.7%和16.8%,而本文提出的基于形状因子的等效热阻模型计算结果与数值模拟计算结果相对误差较小,最大不超过2%.

    Abstract:

    An equivalent thermal resistance model for the heat transfer calculation of radiant floor based on shape factor was developed in this study. The proposed model was verified by numerical simulation, and compared with the data from the universal single power function of ISO standard, the fin model in ASHARE handbook, and the equivalent thermal resistance model in design handbook. The heat transfers obtained by the numerical simulation disagreed significantly with the existing methods including the universal single power function of ISO standard, the fin model in ASHARE handbook, and the equivalent thermal resistance model in design handbook. The maximum error rates were 20.2 %, 30.4 %, and 22.8 %, respectively, when the tube space ranges from 50 to 250 mm, the thickness of fill layer above pipe ranges from 25 to 65 mm, and the average hot water temperature ranges from 25 to 45 ℃. On the other hand, the maximum difference of the heat transfer predictions between the proposed model and the simulation software was less than 3%. When the tube space ranges from 50 to 200 mm, the thickness of fill layer above pipe ranges from 15 to 55 mm, and the average cold water temperature ranges from 10 to 20 ℃, the maximum error rates of the heat transfer predictions between the numerical simulation and the existing methods were 80.1 %, 17.7 %, and 16.8 %. On the other hand, the heat transfer predicted by the proposed model showed less than 2 % of difference from that of the numerical simulation.

    参考文献
    相似文献
    引证文献
文章指标
  • PDF下载次数:
  • HTML阅读次数:
  • 摘要点击次数:
  • 引用次数:
引用本文

吴小舟,赵加宁,王沣浩.基于形状因子的辐射地板传热量计算等效热阻模型[J].湖南大学学报:自然科学版,2016,43(5):137~143

复制
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2016-06-03
  • 出版日期:
作者稿件一经被我刊录用,如无特别声明,即视作同意授予我刊论文整体的全部复制传播的权利,包括但不限于复制权、发行权、信息网络传播权、广播权、表演权、翻译权、汇编权、改编权等著作使用权转让给我刊,我刊有权根据工作需要,允许合作的数据库、新媒体平台及其他数字平台进行数字传播和国际传播等。特此声明。
关闭