+高级检索
基于RC简化传热模型的混凝土辐射顶板传热及供冷能力研究
DOI:
作者:
作者单位:

作者简介:

通讯作者:

基金项目:


Research on Heat Transfer and Cooling Capacities of Concrete Radiant Ceiling Based on Simplified RC-Network Model
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
    摘要:

    为研究混凝土冷辐射板的传热情况并对其供冷能力进行分析,采用RC简化传热模型建立混凝土辐射板二维稳态的传热模型,对混凝土辐射板内部传热情况进行模拟,计算得到混凝土内部及表面温度场.根据计算结果分析不同供水温度、埋管间距情况下,冷顶板表面的温度分布情况及供冷能力.经过实验验证,RC简化传热模型对板内温度和供冷能力的计算误差小于6%;混凝土冷辐射板供冷能力受供水水温、埋管间距及流量的直接影响,当供水温度为11~14 ℃,总流量为0.26~0.33 m3/h,室内空气温度为25~26 ℃时,混凝土辐射板平均供冷量为40~50 W/m2.

    Abstract:

    This paper aims to study the characteristics of heat transfer for concrete radiant ceiling and its cooling capacity. A two-dimensional stead-state heat transfer model on the basis of simplified RC (Resistance and Capacity) Method was adopted to simulate the inner heat-transfer condition of concrete ceiling as well as the temperature fields. The calculated results showed that the cooling capacity of concrete radiant ceiling was affected by the temperature of supply water, distance of tubes and water flow rate. When the supply water temperature, flow rate and indoor air temperature ranged from 11~14 ℃, 0.26 ~0.33 m3/h and 25~26 ℃, respectively, the cooling capacity varied from 40 to 50 W/m2. The simulation models were also validated by experimental results, and the calculation error was less than 6%.

    参考文献
    相似文献
    引证文献
文章指标
  • PDF下载次数:
  • HTML阅读次数:
  • 摘要点击次数:
  • 引用次数:
引用本文

李念平,潘楚阳,黄小君,顾昭阳,苏林,常丽娜.基于RC简化传热模型的混凝土辐射顶板传热及供冷能力研究[J].湖南大学学报:自然科学版,2017,44(3):143~150

复制
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2017-03-24
  • 出版日期:
作者稿件一经被我刊录用,如无特别声明,即视作同意授予我刊论文整体的全部复制传播的权利,包括但不限于复制权、发行权、信息网络传播权、广播权、表演权、翻译权、汇编权、改编权等著作使用权转让给我刊,我刊有权根据工作需要,允许合作的数据库、新媒体平台及其他数字平台进行数字传播和国际传播等。特此声明。