输电线路两相短路故障的自适应分相重合闸方法
DOI:
作者:
作者单位:

作者简介:

通讯作者:

基金项目:


An Approach to Adaptive Sequential Reclosure of Two Phase Short Circuit Fault in Transmission Lines
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
    摘要:

    针对不带并联电抗器的超高压输电线路上发生的两相短路故障,提出一种自适应分相重合闸方法.搭建两相短路故障分析电路模型,推导出瞬时性故障下不同阶段选跳相端电压的时域表达式,分析选跳相端电压特性.研究发现,瞬时性故障二次电弧熄弧时,选跳相断路器两端电压的相角差由-120°突变到180°,且熄弧后恢复电压中出现明显的衰减直流分量.利用选跳相端电压的上述特征,提出了二次电弧熄灭时刻捕捉判据,实现了超高压输电线路上的自适应分相重合闸,并通过仿真验证了分析结果的正确性及所提方法的有 效性.

    Abstract:

    For the phase-to-phase short circuit fault occurred in transmission lines without shunt reactor, a method of adaptive sequential reclosure is proposed in this paper. A circuit model is built for analyzing the phase-to-phase short circuit fault, and the time domain expression of terminal voltage is deduced for the open-phase at different stages of transient fault. The recovery voltage characters of terminal voltage at open-phase is analyzed in detail. The theoretical analysis shows that the phase angle difference of terminal voltage at open-phase changes suddenly from -120° to 180° in the moment of arc extinction, and the decaying DC component appears obviously in the recovery voltage after the arc extinction. According to the above characteristics of terminal voltage at open-phase, a criterion was proposed to detect the arc extinction time and realize the adaptive sequential reclosure of transmission line. The simulations verified the correctness of the analysis result and the validity of the proposed method.

    参考文献
    相似文献
    引证文献
文章指标
  • PDF下载次数:
  • HTML阅读次数:
  • 摘要点击次数:
  • 引用次数:
引用本文

江亚群,洪俊宇,黄 纯,高云鹏,江 辉.输电线路两相短路故障的自适应分相重合闸方法[J].湖南大学学报:自然科学版,2018,45(4):82~88

复制
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2018-04-26
  • 出版日期:
作者稿件一经被我刊录用,如无特别声明,即视作同意授予我刊论文整体的全部复制传播的权利,包括但不限于复制权、发行权、信息网络传播权、广播权、表演权、翻译权、汇编权、改编权等著作使用权转让给我刊,我刊有权根据工作需要,允许合作的数据库、新媒体平台及其他数字平台进行数字传播和国际传播等。特此声明。
关闭