+高级检索
冷弯薄壁型钢拼合箱形截面短柱承载力叠加法
DOI:
作者:
作者单位:

作者简介:

通讯作者:

基金项目:


Superposition Method for Bearing Capacity of Cold-formed Thin-walled Steel Built-up Box Section Short Columns
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
    摘要:

    基于中国规范GB 50018—2002中的有效宽度法和北美规范中的有效宽度法及直接强度法,利用已有的试验数据和文章中有限元参数分析结果,计算了66根通过ST4.8自攻螺钉将单肢C形及单肢U形截面构件连接而成的冷弯薄壁型钢(CFS)拼合箱形截面短柱局部屈曲的承载力. 理论值与试验和有限元值比较分析表明:中国规范GB 50018—2002和北美规范有效宽度法计算结果偏于保守,而北美规范直接强度法可以准确预测构件的承载力,但会存在不安全现象. 基于以上结果,给出了关于冷弯薄壁型钢拼合箱形截面短柱局部屈曲承载力的计算方法——叠加法,并提出了关于CFS拼合箱形截面轴压短柱的理论计算公式. 然后依据48根有限元试件的变参数结果,回归分析得出理论计算公式的组合系数α,得到计算拼合柱极限承载力的公式. 最后通过与试验数据及中美规范计算结果对比,验证了承载力叠加法的适用性与准确性,也为CFS拼合箱形截面短柱承载力的计算提供了简易的方法.

    Abstract:

    Based on the effective width method (EWM) in the Chinese code GB50018-2002 and the EWM and direct strength method (DSM) in the North American code , the local buckling bearing capacity of 66 cold-formed thin-walled steel (CFS) built-up box section short columns composed of C-section and U-section assembles connected by ST4.8 self-tapping screws was calculated by using the available results from experiment and finite element parametric analysis. The comparison between theoretical values and experimental and finite element (FE) values shows that the calculation results obtained from the EWM in GB50018-2002 and American Iron and Steel Institute (AISI) are conservative, while the results calculated by DSM are accurate but unsafe. Based on the above results, a superposition method was presented, and a theoretical calculation model for CFS built-up box-section short columns failed in local buckling under axial compression was proposed. Then,according to the variable parameter results of 48 finite element specimens, the combination coefficient(α) of the theoretical calculation formula was obtained from regression analysis, and the formula for calculating the ultimate bearing capacity of the built-up columns was obtained. Finally, the applicability and accuracy of the proposed design method were verified by comparing with the test data and the calculation results of Chinese and American codes. It also provides a simple method for calculating the bearing capacity of CFS built-up box-section short columns.

    参考文献
    相似文献
    引证文献
文章指标
  • PDF下载次数:
  • HTML阅读次数:
  • 摘要点击次数:
  • 引用次数:
引用本文

周天华,李艳春?覮,吴函恒,桑刘睿,张蕾.冷弯薄壁型钢拼合箱形截面短柱承载力叠加法[J].湖南大学学报:自然科学版,2020,47(11):46~55

复制
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2020-11-23
  • 出版日期:
作者稿件一经被我刊录用,如无特别声明,即视作同意授予我刊论文整体的全部复制传播的权利,包括但不限于复制权、发行权、信息网络传播权、广播权、表演权、翻译权、汇编权、改编权等著作使用权转让给我刊,我刊有权根据工作需要,允许合作的数据库、新媒体平台及其他数字平台进行数字传播和国际传播等。特此声明。
关闭