+Advanced Search

Average Fluid Temperature Used to Calculate Borehole Thermal Resistance of Ground Heat Exchanger
Author:
Affiliation:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
    Abstract:

    A -p--linear dimensionless average fluid temperature was proposed to estimate borehole thermal resistance. A -p--linear dimensionless fluid temperature and the -p--linear dimensionless average fluid temperature were introduced, and the -p--linear dimensionless fluid temperature was compared with theoretical dimensionless fluid temperature calculated by quasi-three-dimensional model for both single and double U-tubes. Results show that the -p--linear dimensionless temperatures with parameters -p-→0 and -p-= -1/2 are respectively in good agreement with the theoretical dimensionless fluid temperatures of single and double U-tubes. Therefore, the dimensionless logarithmic mean temperature for -p-→0 and the dimensionless geometric mean temperature for -p-= -1/2 should respectively be adopted to reasonably estimate the thermal resistance of single and double U-tube boreholes.

    Reference
    Related
    Cited by
Article Metrics
  • PDF:
  • HTML:
  • Abstract:
  • Cited by:
Get Citation
History
  • Received:
  • Revised:
  • Adopted:
  • Online:
  • Published: