+Advanced Search

Algorithm of Room Input Exergy and Application Analysis of Exergy Cost for Air Carrying Energy Radiant Air-conditioning System
Author:
Affiliation:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
    Abstract:

    Based on the heat transfer process of orifice plate and the exergy analysis method of traditional mental radiant panel and convective air-conditioning terminal, the algorithm of room input exergy for air carrying energy radiant air-conditioning system(ACERS) was proposed. The exergy cost analysis model of ACERS was established by exergy cost analysis method. The unit exergy cost of three radiant air-conditioning systems including ACERS, capillary radiant air conditioning system and a combined system of split air conditioning with floor radiant air conditioning,was compared under the premise of thermal comfort. The results show that the unit exergy costs of capillary radiant air conditioning system are 1~3 times higher than that of ACERS in office buildings. The unit product exergy cost for the year of a combined system of split air conditioning with floor radiant air conditioning is 1.2 times higher than that of ACERS in residential building. It is found that the overall exergy economic performance of ACERS is superior to the other two radiant air-conditioning systems, which is of great significance for future engineering application of ACERS.

    Reference
    Related
    Cited by
Article Metrics
  • PDF:
  • HTML:
  • Abstract:
  • Cited by:
Get Citation
History
  • Received:
  • Revised:
  • Adopted:
  • Online: January 23,2019
  • Published: